XWEB 3000 – rel.1.7–
88/136 1592010600
The information provided is: in the past two days (between 24/06 and 26/06, look at “period”), the
system calculated the average set-point “SP1” and the average temperature “Avg”. Moreover it
displays the minimum, the maximum value and the maximum value of temperature after a defrost
(Tdef). Finally it shows the percentage of cool “%Cool”. The latter is the most important value, it is
calculated by using the following math formula:
100%
=
DEFROST
COOL
TT
T
Cool
COOL
T = cool time (corresponding relay open), in the selected time interval
T
= time interval selected
DEFROST
T = defrost time in the selected interval
To complete the information provided this tool show also a horizontal bar and a Legenda. If the
user moves the mouse pointer above this area, the cursor will show the temperature and the data.